Mufidzade N.A., Agayev I.E.

  


INVESTIGATION OF THE MAIN CHARACTERISTICS AND ELECTRICAL STRENGTH OF TRANSFORMER CIRCUIT INSULATION *

  


Аннотация:
assessment of the wear condition of transformer insulation is one of the main conditions for their normal and long-term operation. Depreciation directly depends on the operating temperature of the equipment, external influences on them and the duration of operation. During operation, the main disadvantage is that the insulation loses its quality due to wear and tear. This increases the moisture in the Transformer during the aging process, further accelerating the aging process. Knowing the moisture content of solid insulation, getting an idea about the degree of wear and tear and its further operation can be decided. Various methods of frequency spectroscopy (FDS) are known. The service life of the power transformer is its structural materials It also depends on the temperature. Temperature processes in the transformer Due to their significant impact, comprehensive information about these processes is of great interest.   

Ключевые слова:
insulation, transformer winding, electrical strength, insulation resistance   


DOI 10.24412/2712-8849-2024-271-516-521

Insulating materials applied to the duct are classified based on how long they can withstand heat. As we know, every time the load increases, the temperature of the circuit increases due to the flowing current. For every 10 degrees increase in temperature, the life of the insulation decreases by 50%. Based on that temperature factor, the insulation composition is divided into classes - fig. 1.Fig. 1. Dependence of insulation tolerance on temperature.Table 1 lists insulation classes and their tolerance temperatures.Table 1. Insulating compositions of coils according to different classes. In general, the temperature of the windings of electric machines during normal operation should not exceed the insulation class specified in their passports. Otherwise, for every 10% increase in temperature, the operating life of the electric machine is halved. For example: If the temperature of the circuit of the electric machine has risen to 1800C, then:Will only work for 300 hours if it is Class A insulation.Will work for 1800 hours if it is Class B insulation.Will last 8500 hours if it is Class F insulation.Will work for 10000 hours if it is class H insulation.The most common accident is that the winding insulation is damaged and a single phase is shorted to earth. Deterioration of insulation is one of the main causes of ground fault. Insulation resistance is measured with a megometer with a voltage of 1000 ... 2500V. The measurement is carried out when the temperature of the top layer of oil is not lower than +100C. They measure the insulation resistance between the cores in each turn, as well as between the turns. During the measurement, the reading of the megometer is taken 15 and 60 seconds after the voltage. At this time, the absorption coefficient is determined as Kab. The value of absorption coefficient in moistened insulation should not be less than 1.3. It is recommended to evaluate the condition of the insulation by comparing the results of the measurements with the preliminary data known in advance at the same temperature. In the absence of initial data, the approximate average operating data of the minimum allowable value of the insulation resistance can be used. According to D?IST 11677-75, the test of electrical strength of transformer insulation is carried out by two methods. They test the head insulation (insulation between windings) of the transformer with normal frequency elevated voltage. At this time, the test voltage is tested, with a short-circuited circuit, all other circuits of the transformer and the magnetic conductor are closed, and is applied between the earthed tank (Fig. 2). The test is carried out after 10 ... 20 hours have passed since the oil was poured into the transformer and when the temperature of the upper layers of the oil is around +200C. First, they try the AG loop and then the YG loop. They increase the voltage intermittently - smoothly, from 0 to the full test voltage. They keep the test voltage until one minute has passed from the moment it is established, and then slowly reduce it. If during the supply of high voltage, there is no perforation of the insulation, no vapor separation, or no decrease in the test voltage, then the transformer is considered to have passed the test (Fig. 2).Fig. 2 Test scheme of the electrical strength of the main (main) insulation of the transformer: TV1 – autotransformer, TV2 – transformer, R – resistor, TV3 - the transformer under test.The test of the longitudinal insulation of the transformer (between the windings, layers and sections) is carried out with a high voltage induced in the transformer itself. This test is carried out in the no-load mode by applying a voltage equal to 1.3 nominal for one minute to the outputs of one of the circuits (usually AG). Each transformer coming out of repair must pass a verification test. Before testing, the transformer is externally inspected and the windings are checked for proper connection. During the external inspection, the insulation quality of the windings of the transformer is carefully checked, the connection of the output ends to the clamp plate and marking are reviewed. In the external inspection process, the general condition of the transformer core, the flat stacking of the sheets, the insulation quality of the winding studs and the quality of the steel sheet retention are evaluated. According to the current standards, small power transformers must undergo the following inspection tests after repair:1) checking the transformation coefficient on all outputs.2) measuring the insulation resistance of the circuit.3) measuring the resistance of the wires of the windings with a constant current.4) testing of electrical strength of circuit insulation.5) measurement of no-load losses and current of the transformer.6) measuring the short-circuit voltage and loss of the transformer.The insulation resistance of the transformer windings to the body should be checked with a megohmmeter with a voltage of up to 500V. The measured value is compared with the previous results. The minimum value of insulation resistance should not be less than 5MOm. In the period of operation, the value of the insulation of the loop measured in the cold state should not be lower than 1MOm. The test of the electrical strength of the winding insulation is carried out according to the following scheme in order to check the insulation between the body and the winding by applying a test voltage in single-phase small power transformers (Fig. 3).Fig. 3. Electrical scheme of the test stand.The trial period is considered to be 1 minute. The test voltage is found from the following expression.Usin = 2Un + 1000where Un is the nominal voltage of the tested circuit of the transformer. The test result is considered positive if the indication of the devices does not change sharply during the test process, and short-circuiting does not occur.Conclusion. In the article, according to the insulation classes of transformer windings, their insulation strength was investigated by several methods. Several factors affecting transformer windings during operation have been studied. The advantages and disadvantages of various methods for measuring the insulation quality of the circuit have been investigated.

  


Полная версия статьи PDF

Номер журнала Вестник науки №2 (71) том 2

  


Ссылка для цитирования:

Mufidzade N.A., Agayev I.E. INVESTIGATION OF THE MAIN CHARACTERISTICS AND ELECTRICAL STRENGTH OF TRANSFORMER CIRCUIT INSULATION // Вестник науки №2 (71) том 2. С. 516 - 521. 2024 г. ISSN 2712-8849 // Электронный ресурс: https://www.вестник-науки.рф/article/12904 (дата обращения: 17.05.2024 г.)


Альтернативная ссылка латинскими символами: vestnik-nauki.com/article/12904



Нашли грубую ошибку (плагиат, фальсифицированные данные или иные нарушения научно-издательской этики) ?
- напишите письмо в редакцию журнала: zhurnal@vestnik-nauki.com


Вестник науки СМИ ЭЛ № ФС 77 - 84401 © 2024.    16+




* В выпусках журнала могут упоминаться организации (Meta, Facebook, Instagram) в отношении которых судом принято вступившее в законную силу решение о ликвидации или запрете деятельности по основаниям, предусмотренным Федеральным законом от 25 июля 2002 года № 114-ФЗ 'О противодействии экстремистской деятельности' (далее - Федеральный закон 'О противодействии экстремистской деятельности'), или об организации, включенной в опубликованный единый федеральный список организаций, в том числе иностранных и международных организаций, признанных в соответствии с законодательством Российской Федерации террористическими, без указания на то, что соответствующее общественное объединение или иная организация ликвидированы или их деятельность запрещена.